Dark Light

GIGANET GN-UIC100L 10kVA/8kW Three Phase Online UPS


  • True online double conversion design
  • Build-in input and output transformer with strong galvanic isolation
  • Wide input range, avoid frequently transfer to battery mode, prolong
    the battery lifetime
  • With parallel function, flexibly response to the expansion and redundancy requirement
  • Intelligent battery management technology, fully protect battery
  • Battery cold start function
  • Comprehensive and reliable protection

GIGANET GN-UIC100L 10kVA/8kW Three Phase Online UPS

Specifications

ModelGN-UIC60LGN-UIC80LGN-UIC100LGN-UIC150LGN-UIC200LGN-UIC300LGN-UIC400L
Capacity VA/Watts6kVA/4.8kW8kVA/6.4kW10kVA/8kW15kVA/12kW20kVA/16kW30kVA/24kW40kVA/32kW
INPUT
Operating Voltage Range380Vac(±20%), (3Ph+N+PE)
Operating Frequency Range50/60Hz (±5%)
Power Factor>0.97 (with filter)
Max.Input Current(A)14182334456890
OUTPUT
Output Voltage220Vac(1±1%)
Output frequency50/60Hz(1±1%)
Crest factor3:1(max)
Efficiency6~8KVA: 85% online 10~40KVA: 90% online
Harmonic Distortion (THDv)<1.5% with linear load
BATTERY
Battery voltage192Vdc240Vdc
SYSTEM FEATURES
Transfer timeUtility Battery : Oms
OverloadLoad≤125%/ 1min; ≤150% /200ms,to Bypass
LED displayBattery low, Mains status, Inverter, Bypass, UPS failure, Overload
LCD displayI/O voltage, Frequency, Battery voltage, Load percentage,Internal temperature
Communication InterfaceRS232, SNMP (optional), Dry contact,RS485
PHYSICAL
Dimension W×D×H (mm)305*585*864409*798**1044555*741*1200600*800*1200
Net Weight(48V/192V)(kg)100110120145155255336
ENVIRONMENT
Operating Temperature0~40°C
Storage Temperature-25℃~55℃
Humidity Range0~95% (Non-condensing)
Altitude<1500m
Noise level<55dB
STANDARDS
SafetyIEC/EN62040-1 ;IEC/EN60950-1
EMCIEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
SKU: OF3178 Category: